Номинальный ток рассматриваемой цепи, A | Минимальная площадь поперечного сечения проводника, мм ![]() |
До 16 включ. | - |
Св. 16 до 25 включ. | 1,5 |
" 25 " 32 " | 2,5 |
" 32 " 40 " | 4,0 |
" 40 " 63 " | 6,0 |
" 63 " 80 " | 10 |
" 80 " 100 " | 16,0 |
" 100 " 125 " | 25,0 |
" 125 " 160 " | 35,0 |
" 160 " 190 " | 50,0 |
" 190 " 230 " | 70,0 |
" 230 " 260 " | 95,0 |
" 260 " 300 " | 120,0 |
" 300 " 340 " | 150,0 |
" 340 " 400 " | 185,0 |
" 400 " 460 " | 240,0 |